Screwed Ball Float Steam Trap FT14
Reference FOB Price: US $30-100 / Piece
Min. Order: 10 Pieces
Port: Ningbo, China
Production Capacity: 50000 PCS/Ye
Payment Terms: L/C, T/T
Pressure: Low Pressure
Temperature: Ordinary Temperature
Connection: Thread
Material: Cast Steel/Stainless Steel
Type: Ball Float
Mini Working Pressure: 0.01MPa
Screwed Ball Float Steam Trap FT14 pictures & photos
  • Screwed Ball Float Steam Trap FT14
  • Screwed Ball Float Steam Trap FT14
  • Screwed Ball Float Steam Trap FT14
Basic Info
  • Model NO.: FT14
  • Valve Seat: Stainless Steel
  • Pin: Stainless Steel
  • Cover Gasket: Graphite
  • Trademark: XIUTAI
  • Specification: ANSI
  • HS Code: 8481804090
  • Valve Body, Cap: Cast Steel/Stainless Steel
  • Working Medium: Saturated Vapor, Condensed Water
  • Ball Float and Lever: Stainless Steel
  • Size: 1/2"-1"
  • Transport Package: Plywood Case
  • Origin: Wenzhou
Product Description
Screwed Ball Float Steam Valve
 
The FT14-T is  ball float steam trap having stainless steel working internals and integral automatic air venting facility. The FT14-T can be maintained without disturbing the pipework.
Available types
FT14 (R-L) Horizontal connections with flow from right to left
FT14 (L-R) Horizontal connections with flow from left to right


Sizes and pipe connections
½", ¾" and 1" screwed BSP or NPT.


 
Limiting Condition
Body design conditions PN16
PMA  Maximum allowable pressure 16 bar g @ 100°C
TMA  Maximum allowable temperature250°C @ 13 bar g
Minimum allowable temperature-10°C
PMO  Maximum operating pressure for saturated steam service14 bar g
TMO  Maximum operating temperature250°C @ 13 bar g
Minimum operating temperature0°C
PMX  Maximum differential pressureFT14-4.54.5 bar
FT14-1010 bar
FT14-1414 bar
Designed for a maximum cold hydraulic test pressure of 24 bar g


Material: 
Body:A216 WCB          
Bonnet:A216 WCB
Seat:Stainless Steel              
Ball Float and Lever:Stainless Steel  


Capacities






Screwed Ball Float Steam Trap FT14
                                                                        
Capacities shown above are based on condensate at saturation temperature. When discharging sub-cooled condensate the air vent provides extra capacity. Under start-up conditions when the condensate is cold the internal thermostatic air vent will be open and provides additional capacity to the main valve. On 4.5 bar units this will provide a minimum of 50% increased capacity above the hot condensate figures shown. On 10 and 14 bar units this will be a minimum increase of 100% on the published capacity. The above table gives the minimum additional cold water capacities from the air vent.


Screwed Ball Float Steam Trap FT14